Answer:
displacement power factor is 0.959087
Explanation:
given data
THD = 88%
true power factor = 0.72
solution
we get here total harmonic distribution THD is express as here
THD = [tex]\sqrt{\frac{1}{g^2}-1}[/tex] Â Â Â ..............1
her g is distortion factor
so put here value and we will get g that is
0.88² =  [tex]\frac{1}{g^2} -1[/tex]  Â
solve it we get
g = 0.750714
and
displacement power factor is express as
DPF = [tex]\frac{PF}{g}[/tex] Â .................2 Â
put here value and we will get
DPF = [tex]\frac{0.72}{0.750714}[/tex] Â Â
DPF Â = 0.959087